This paper presents an investigation into the virtualization of substation protection IED functions using a sophisticated co-simulation environment that integrates virtual intelligent electronic devices (vIEDs) with a real-time power grid simulation. Anchored by the IEC 61850 protocol, this study constructs a virtualized IED framework, emphasizing the encapsulation of protection schemes using the example of different types of overcurrent protection within a containerized vIED. Using open-source software, this study aims to replicate the communication and functional aspects of physical IEDs. This study uses a co-simulation environment that couples virtualized network components with a real-time power grid simulation to validate the vIEDs against real substation hardware. Simulation results from induced short-circuit events confirm the operational congruence of the vIEDs with their physical counterparts, demonstrating their potential to serve as cost-effective and adaptable testbeds for substation automation. This paper concludes that virtualized IEDs represent a cost-effective, flexible alternative for substation automation testing, with future research directed towards increasing the functional complexity and real-world applicability of these virtual systems.
No takes yet. Share an insight, caveat, or question.
Rösch et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: