Pool boiling plays a vital role in refrigeration systems with flooded evaporators. Due to the necessary lubrication of the compressor, oil is transported into the refrigeration circuit in addition to the refrigerant. In this study the influence of different polyester oils on the evaporation of R134a and R1234ze(E) is examined on an enhanced tube. Heat flux was varied between 25 kW/m² and 45 kW/m², while saturation temperatures of 3 °C, 7 °C and 11 °C with oil mass fractions of up to 4 m% were examined. The POE oil SE170 with R134a shows the strongest effect on the heat transfer coefficient. With SE55 and R134a for low saturation temperature, low heat flux and 0.5 m% oil mass fraction a slight increase can be investigated. The main influence of oil can be attributed to the change in viscosity of the mixture. Furthermore, a correlation-based model is provided to predict the outer and overall heat transfer coefficient including the influence of oil. The outer heat transfer coefficient can be predicted within an absolute average percentage error (AAPE) = 6.9% and AAPE = 2.5% for the overall heat transfer.
No takes yet. Share an insight, caveat, or question.
Möhrle et al. (2024) studied this question.