This analysis identifies benefits of virtual synchronous generator integration for transient stability in microgrids, suggesting improved system planning.
Stability enhancement in microgrid systems poses significant challenges, especially with high penetration of inverter-based resources. This paper proposes the integration of Virtual Synchronous Generators (VSGs) into microgrids to provide additional virtual inertia, thereby improving system stability during disturbances. A quantitative transient stability assessment based on Critical Clearing Time (CCT) is introduced to comprehensively evaluate system dynamics with VSG integration. CCT serves as a practical metric for determining the maximum allowable fault-clearing time to maintain stability, with the CCT value derived through fault trajectory analysis using the fourth-order Runge-Kutta numerical method. Resulting trajectories are classified as Stable Trajectory (ST) or Unstable Trajectory (UT) based on post-fault system response. The study is conducted on a modified IEEE 9-bus microgrid system comprising three diesel generators, with VSG integration modeled under two penetration scenarios: 11% and 29%. Simulation results show that VSG integration significantly enhances transient stability margins. However, system response is highly sensitive to fault location and duration, underscoring the need for careful system planning.