A power outage of the distribution network could cause large economic losses and safety hazards for industrial companies. Therefore, many industrial companies have a backup power source. Nevertheless, without automatic transition between grid-connected and islanded modes, there will be some time of outage of all consumers. In this article, calculations of the system average interruption duration index (SAIDI) were done and how it changes when automatic transition will be available. The low voltage and medium voltage SAIDI index values for the Czech largest distribution network operator were used as basic values for the calculations. It was calculated that the SAIDI index will improve from 307 min/year to 32 min/year with CHP as the hot reserve at a low voltage level and from 331 min/year to 35 min/year at a medium voltage level. It means a huge improvement in the reliability of the electric power supply. Automatic transition systems are especially worthwhile for companies and plants for whom interruption of production is very costly or a safety hazard.