The ESS cryogenic Moderator System (CMS) has been designed to supply a subcooled liquid hydrogen (17.5 K and 1.0 MPa) to two hydrogen moderators where the nuclear heating is estimated to be 6.7 kW (to be increased to four in the future). The CMS is cooled by a helium refrigerator system with a cooling power of 30.3 kW at 15 K. In this study, a one-dimensional simulation code has been developed to understand temperature behaviors during the cool-down process. The operational methods and parameters have been optimized. The CMS cool-down process is divided into three phases (I: gaseous hydrogen above 36 K, II: condensation from 36 to 31 K, and III: liquid hydrogen below 31 K). It turns out from the simulation result that the CMS would be able to be cooled down to the nominal condition of 17 K within 27 hours.
No takes yet. Share an insight, caveat, or question.
Tatsumoto et al. (2024) studied this question.
Synapse has enriched one closely related paper. Consider it for comparative context: