To comply with the development of the “dual-carbon” goal, a new refrigerant for heat pump products is necessary. Firstly, mathematical models of enhanced vapor injection air energy heat pump and transcritical CO 2 heat pump systems were established, and they were calculated using thermodynamic methods. The results show that when CO 2 is used as the refrigerant, the discharge temperature is 30% and 22.7%, which is higher than that of R410A and R134a, and 4.9% lower than that of R32. At the compressor outlet, the volume flow rate of CO 2 is 59.0%, 60.8%, and 64.2% less than R410A, R32, and R134a, respectively. In terms of power consumption, the difference between CO 2 and R410 A is within 6%. The power consumption of the CO 2 system is 0% ∼ 6.4% higher than that of the R32 system and 29.2% ∼ 46.5% lower than that of the R134a system. The COP of the CO 2 system is within 6% of that of the R410A and R32 systems, which is 41% ∼ 87% higher than that of the R134a system. When the ratio of CO 2 / R32 is 0 ∼ 0.2 and 0.9, the COP of the mixed refrigerant is better than that of the single refrigerant CO 2 .