To evaluate the operation status of air insulated switchgears (AIS), this work purposes N- and Pd- embedded graphene (N- and Pd-graphene) as potential gas sensors upon two typical faults gases (CO and NO 2 ) from the first-principles simulations. It is found that the N and Pd atoms can be stably trapped on the C-vacancy of the C-defected graphene with the formation energy of −12.17 and −5.12 eV, respectively. N-graphene behaves physisorption towards CO and NO 2 molecules while Pd-graphene behaves chemisorption instead. The resistance-type and work function (WF)-based sensing mechanisms of N- and Pd-graphene upon such two gas species are illustrated and uncovered by analyzing their deformations of electronic property and WF in the gas adsorption systems, which reveals the potential of Pd-graphene as a resistive CO and NO 2 sensor, N-graphene as a resistive NO 2 sensor, as well as the N- and Pd-graphene as WF-based gas sensor for NO 2 detection. This work highlights the comparison of adsorption and sensing performances between N- and Pd-graphene upon two typical gas sensors in AIS, which would be meaningful to explore novel graphene-based sensing materials facilitating their investigations and applications in the power system.
No takes yet. Share an insight, caveat, or question.
Wu et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: