The authors propose an intelligent location sensing system which automatically detects problems in the power supply network and takes measures to prevent accidents. The decision-making algorithm is based on pulse sensing of overhead power lines. The location equipment is connected to 35 - 750 kV air lines via connection filter and a high-voltage communication capacitor, which transmit technological information from relay protection and emergency automation equipment to the high-frequency path of the line. For overhead lines that do not have such equipment, location pulses can be applied via a lightning protection cable (ground wire) provided on 35 - 750 kV lines. Simulation of this process in PSCAD system shows that the energy of microsecond-long sounding pulses is sufficient for effective and reliable detection of damage to the line wires.
No takes yet. Share an insight, caveat, or question.
Minullin et al. (2024) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: