Answers are grounded in this paper and cite their sources.
Heat-transfer enhancement and entropy generation were investigated for a double-helical-type-channel heat sink with different rib structures set on the upper wall. Based on available experimental data, a series of simulations with various turbulence models were conducted to find the best numerical model. Five different rib structures were considered, which were diamond (FC-DR), rectangular (FC-RR), drop-shaped (FC-DSR), elliptic (FC-ER) and frustum (FC-FR). The research was carried out under turbulent flow circumstances with a Reynolds number range of 10,000–60,000 and a constant heat-flow density. The numerical results show that the thermal performance of the flow channel set with a rib structure is better than that of the smooth channel. FC-ER offers the lowest average temperature and the highest temperature uniformity, with a Nusselt number improvement percentage ranging from 15.80% to 30.77%. Overall, FC-ER shows the most excellent performance evaluation criteria and lowest augmentation entropy-generation number compared with the other reinforced flow channels.
No takes yet. Share an insight, caveat, or question.
Liyi et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: