We used the liquid-based R2 rotational seismometer in addition to several arrays of translation velocity seismometers on a 12-floor building in the National Cheng Kung University campus to evaluate the dynamic responses of the structure. During the observation period in August-October 2023, we encountered a moderate M 5.6 earthquake sequence 61 km north of the campus and one moderate typhoon passing through this 49-m-long and 12-m-wide building. By examining these data, we investigate the natural frequency and the rotation behavior of the long-strip-shaped building. Both the time-frequency and Fast Fourier Transform analyses of the microtremor and earthquake data show two dominant frequencies of ~1.2 Hz and 1.8 Hz occurred in the horizontal directions. The translation velocity and rotation rate are more significant in the transverse, short-axis direction and at the location away from the elevator of the building. The translation velocity array and rotational seismometer show rotations around the horizontal and vertical axes during the M 5.6 earthquake. The results of two natural frequencies and the corresponding rotational motions are most likely related to the asymmetric design of the building, which resulted in the non-rigid behavior of the structure. These findings may provide insights into improvements that could enhance the building’s resilience to seismic or typhoon events.