Experimental results demonstrate vibration suppression in indoor substations, indicating the effectiveness of the inertial actuator approach.
This paper addresses the suppression of multi-frequency line spectrum vibrations during the operation of indoor substations through the development of an active vibration isolation scheme based on a piezoelectric stack inertial actuator. Based on the finite element modal analysis, the excitation frequencies that strongly influence structural response were identified, and the excitation points and sensor layout strategies were determined under a collocated control configuration. Subsequently, the actuator’s structural design and system integration were carried out. Experimental results demonstrate vibration amplitude reductions of 18.75 dB at 100 Hz, 46.02 dB at 200 Hz, and 32.04 dB at 300 Hz, respectively, validating the effectiveness of the proposed method in controlling line spectrum vibrations at multiple frequencies. The study shows that the coordinated optimization of modal matching and the dynamic response capability of inertial actuators provides experimental evidence and technical guidelines for active vibration isolation in large plate-shell structures.
No takes yet. Share an insight, caveat, or question.
Li et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: