October 19, 2025Energies2 citationsOpen Access

Experimental Methods and Equivalence Research on Inter-Turn Short Circuits in Power Transformers

View Full Paper
SZShichao ZhangCYChun YangYSYuanming Shuai

Key Points

  • Simulation results show that the proposed fault model aligns closely with actual conditions, with errors under 5%.
  • An experimental platform was built to simulate inter-turn faults, facilitating detailed analysis of short-circuit behavior.
  • Both primary/secondary winding currents and leakage magnetic fields were measured, confirming the accuracy of the simulation.
  • This approach enhances understanding of transformer fault characteristics through innovative simulation methodologies.

Abstract

Inter-turn short-circuit faults in power transformers generate enormous short-circuit currents within the affected turns, making full-scale experimental investigations impractical. To address this issue, this study proposes an experimental method utilizing a third external short-circuit winding to simulate inter-turn faults through structural improvements in winding configuration and conductor current-carrying capacity. A simulation calculation model for transformer inter-turn short circuits was first established to investigate the equivalence between the proposed equivalent fault model and actual fault conditions under varying short-circuit positions and proportions. Simulation results demonstrate that both models exhibit consistent primary/secondary winding currents, short-circuit turn currents, and spatial radial leakage magnetic field distributions post-fault, with average errors less than 5%. Subsequently, an experimental platform for inter-turn short-circuit fault simulation was constructed. Current and leakage magnetic field measurements under different fault positions and proportions were validated against simulation data, confirming the proposed method’s equivalence. This approach provides an effective pathway for investigating fault characteristics and monitoring methodologies of transformer inter-turn short circuits.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Zhang et al. (2025) studied this question.