Simulation modeling identifies corrosion impact on grounding grids, suggesting improved fault location strategies.
The grounding grid of a substation is a crucial component for ensuring normal operation. However, since it is buried underground for long periods, it is highly susceptible to electrochemical corrosion. This corrosion leads to a reduction in its grounding performance, and severe corrosion may endanger the reliable operation of high-voltage equipment and secondary relay-protection equipment, as well as the safety of personnel. In this paper, the electromagnetic field analysis method is used to conduct simulation modeling of the grounding grid. A different-frequency current is injected into the grounding grid to study the variation law of the surface magnetic field distribution when corrosion occurs to different degrees at different positions in the grounding grid. Through the analysis of the evolutionary characteristics of the magnetic field distribution, the corrosion-induced breakages in the grounding grid are located and a comprehensive state evaluation is carried out. The results show that when a fault occurs in a conductor at the same position, the variation amplitude of the surface magnetic field gradually increases with increased corrosion. Based on this finding, an online monitoring algorithm for the location of corrosion-induced breakages and state evaluation of the grounding grid is proposed. A comprehensive evaluation model is constructed by combining the grounding resistance value and corrosion characteristic value to accurately locate the fault.
No takes yet. Share an insight, caveat, or question.
Xue et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: