Novel arc fault detection method demonstrates high precision in recognizing faults in AC systems, indicating significant improvement in safety and reliability.
This paper proposes a novel AC side series arc fault (SAF) identification method based on Generalized Lissajous Trajectory (GLT) learning for low-voltage residential circuits. The method addresses challenges in detecting SAFs—characterized by high concealment, random occurrence, and limitations in existing protection devices—by leveraging the Hilbert transform to map current signals into 2D Generalized Lissajous Trajectories. These trajectories amplify key SAF features (e.g., zero-break distortion and random pulses). A ResNet50-based image recognition model achieves high-precision fault detection under specific load types, with a validation accuracy of up to 99.91% for linear loads and 98.93% for nonlinear loads. The algorithm operates within 1.6 ms, enabling real-time circuit breaker tripping. The proposed method achieves higher recognition accuracy with lower computational cost compared to other image-based methods. In this paper, an adjustable load signal modeling approach is proposed to visualize the current signal using GLT and complete the lightweight identification based on ResNet network, which provides new ideas and methods for series arc fault detection.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2025) studied this question.