Ensuring thermal comfort in waiting areas is essential for visitor satisfaction and well-being. In the context of nearly zero-energy buildings (nZEBs), these spaces—typically characterized by short-term occupancy, transient user behavior, and the need for rapid temperature adjustment—pose specific challenges for HVAC control in balancing comfort and energy demand. This study investigates the influence of a ceiling-mounted fan coil unit (FCU) operating in heating mode on thermal comfort conditions in an nZEB office waiting area. Measurements were conducted at multiple points within the space to assess microclimate parameters, followed by the calculation of the predicted mean vote (PMV) and predicted percentage of dissatisfied (PPD) indices, supported by occupant feedback collected through short interviews. The results showed that although the FCU effectively increased the average temperature, its intermittent operation and localized air jets during the heating phase caused temporary discomfort near the unit. Occupant feedback confirmed sensations of discomfort due to strong air movement during FCU operation but indicated slightly higher overall dissatisfaction and smaller variability compared to model-based PPD values, reflecting the averaging effect of occupant perception over time. These findings highlight the need for optimized FCU control strategies in waiting areas, such as operating at reduced fan speeds and preheating the heat exchanger, to enhance occupant comfort. This study contributes to improving HVAC control concepts for semi-transient spaces in nZEBs.
Fedorczak-Cisak et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: