The long-term operational stability of a fiber optic current transformer (FOCT) is critically dependent on the integrity of its internal fiber optic loop. Conventional testing methods often fall short in providing high-precision, spatially resolved diagnosis of FOCT internal fiber links. To overcome this limitation, this paper proposes a distributed sensing and testing scheme based on Optical Frequency Domain Reflectometry (OFDR). The implemented OFDR system offers a measurement range of up to several hundred meters, with a spatial resolution of 10 μm and a localization accuracy of 1 mm. Capitalizing on these capabilities, the proposed approach enables a comprehensive inspection of the FOCT sensing coil and lead fibers. At the same time, the OFDR response of various devices in the FOCT system is analyzed, while providing precise measurements of both optical loss and reflectance. In addition, the temperature stress variation of the sensing coil is measured by using the sensing characteristics of OFDR. This work provides a powerful and indispensable tool for FOCT factory testing, field fault diagnosis, and condition monitoring, contributing significantly to the safety and stability of smart grid systems.
No takes yet. Share an insight, caveat, or question.
Wen et al. (2025) studied this question.