This study reports the thermodynamic performance of a patented compact vertical evaporator–absorber unit for LiBr–H2O absorption cooling, extending Part I by translating validated prototype data into a rigorous control-volume assessment of coupled transport. Coolant-side calorimetry was used to determine the absorption heat-transfer rate (Qabs), while a mass–energy balance provided an estimate of the absorption mass-transfer rate (∆m˙abs) across twelve manually imposed thermal-load phases with tagged fan-OFF/ON sub-intervals. Linear trend (slope) analysis was applied to quantify phase-resolved dynamic behavior. Fan assistance produced three load-dependent regimes: (i) stabilization of downward trends under low and zero loads, yielding slope-based relative improvements above 100% in the most critical weak-gradient phases; (ii) acceleration of recovery at intermediate loads; and (iii) moderation of strongly positive drifts at high loads. The global thermal resistance (Rth) decreased by more than 30% in passive and low-load phases, and Wilcoxon signed-rank tests confirmed statistically significant reductions in most intervals (p < 0.05). Uncertainty contributions and robustness were quantified through an uncertainty budget decomposition and sensitivity analyses, and a subsystem-level normalization (ηEA = Qabs/Qin) is reported to support comparisons across loads without invoking cycle COP. Overall, active vapor-flow management using a low-power internal fan widens the useful operating envelope of compact absorbers and provides a validated thermodynamic baseline with practical, regime-aware control guidelines for decentralized low-carbon cooling technologies.