Micro Partial Discharge Characteristics of SF 6 Under DC Voltage

View Full Paper
GCGeng ChenNorth China Electric Power UniversityJWJie WangNorth China Electric Power UniversityCLChuanyang LiTsinghua University

Key Points

  • This work aims to investigate the characteristics of micro partial discharges in SF6 under varying pressures and voltages.
  • Utilized a highly sensitive micro-discharge measurement platform.
  • Performed experiments at pressures ranging from 0.1 to 0.7 MPa.
  • Analyzed results using time-resolved PD and pulse sequence analysis.
  • Observed a strong polarity effect in micro partial discharges.
  • Mean amplitude and repetition rates peaked at 0.3 MPa.
  • Shifted from negative to positive polarity dominance with increasing voltage.
  • Identified clustered bursts and amplitude stratification patterns.

Abstract

ABSTRACT In gas‐insulated high‐voltage direct current (HVDC) devices, micro partial discharges (PD) caused by micro‐protrusions or surface roughness on conductors or enclosures may not cause immediate insulation system failure due to their weak discharge intensity. However, the continuous charging of carriers generated by the discharges to the insulator is one of the potential triggers of surface flashover of insulators. This work investigates the micro PD characteristics in SF 6 at 0.1–0.7 MPa, which is below the lower limit of conventional detection methods, via a highly sensitive micro‐discharge measurement platform. The experimental results show that the micro PD exhibits a strong polarity effect. With increasing pressure, the mean amplitude and mean repetition rates exhibited an extremum at 0.3 MPa. As the applied voltage increased, the mean amplitude shifted from negative polarity dominance over positive polarity to positive polarity dominance over negative polarity. Time‐resolved PD (TRPD) and pulse sequence analysis (PSA) patterns indicate that the micro PD is characterised by clustered bursts and amplitude stratification. Furthermore, the negative polarity micro PD is more stable than the positive polarity counterpart. The results of this work can provide references to guide the optimized design of gas‐insulated HVDC devices.