Investigates winding damage in power transformers under short-circuit conditions, suggesting new maintenance insights.
Winding damage is one of the most common and highly destructive faults in power transformers. To analyze the winding force and deformation under short-circuit conditions, this paper establishes a three-dimensional simulation model of a 220 kV oil-immersed power transformer. The force distribution of the windings under different short-circuit scenarios is investigated, and the vulnerable locations in different simulation model configurations are identified. The effects of variations in spacer blocks and tie bar quantities, as well as differences in material parameters of each component, on the evolution of weak-force regions are summarized. Finally, the influence of short-circuit cumulative effects on the maximum winding deformation is studied, providing a theoretical basis for transformer condition-based maintenance and fault prediction.
No takes yet. Share an insight, caveat, or question.
Zang et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: