Comparative analysis evaluates energy efficiency in solar-assisted heat pumps, suggesting benefits of integrating photovoltaic cells.
This paper presents a comparative analysis of direct expansion solar-assisted heat pumps (DX-SAHP) with and without photovoltaic cells (PVT-DX-SAHP). Two sets of experiments were conducted to validate the mathematical model: one with PVT-DX-SAHP and another with DX-SAHP. The mathematical model used in this study is based on physical equations using energy, mass, and entropy balance. The heat exchangers were modeled using the moving boundaries technique. The compressor and photovoltaic cells were modeled using a black box model with equations for the efficiencies of these components. The low-global-warming-potential (GWP) refrigerant R290 (propane) was used in this study. Two independent sets of experimental data were used to validate the model, with a mean absolute deviation of 4.8%. The results indicated that PVT-DX-SAHP had a higher season performance factor (SPF) and a lower total equivalent warming impact (TEWI) compared to DX-SAHP, with an average SPF increase of 81% and a TEWI reduction of 30%. The findings also showed that PVT-DX-SAHP had a 24% higher longer payback period than DX-SAHP.