PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
March 21, 2026Energies2 citationsOpen Access

Study on the DC Discharge Model of Insulators Polluted by Typical Components Based on Effective Salt Deposit Density

View Full Paper
WZW. ZhangSPShaoming PanLZLaisheng Zhong

Key Points

  • The aim is to develop a more accurate model for predicting flashover voltage in polluted transmission line insulators using effective salt deposit density.
  • Conducted experiments on the conductivity of electrolyte solutions.
  • Developed a dynamic model based on effective salt deposit density (SDDe) for polluted insulators.
  • Compared calculated flashover voltage with experimental values.
  • Analyzed the effects of different pollution types and surface water adhesion on flashover voltage.
  • The average difference between the calculated and experimental flashover voltage is less than 7%.
  • Flashover voltage decreases with increased insulator surface water adhesion.
  • The proposed model considers slightly soluble pollution and accurately predicts flashover voltage in complex conditions.

Abstract

Pollution flashover accidents of transmission line insulators have a wide impact and low reclosing success rates, posing a serious threat to the safe and stable operation of the power grid. The existing pollution discharge and flashover models of insulator based on equivalent salt deposit density (ESDD) present significant differences from the actual situation. To address this issue, the conductivity of electrolyte solutions experiments is carried out in this paper, and the quantitative functional relationship between conductivity and concentration of typical components is obtained. On this basis, the concept of effective salt deposit density (SDDe) is introduced to characterize the actual mass of pollution participating in surface conduction per unit area. A DC discharge dynamic model for polluted insulators is established and verified based on SDDe combined with the discharge development process. Research results indicate that the average difference between the calculated flashover voltage and experimental value is less than 7%. The deviation of flashover voltage between the SDDe basis model and measured salt deposit density (SDDm) basis value increases with the increasing proportion of slightly soluble components. With the increase of insulator surface water adhesion, the flashover voltage obtained by the proposed model decreases while the corresponding SDDm basis value remains constant. The effects of factors such as slightly soluble pollution and surface water adhesion are considered in the proposed model sufficiently. The application of the model based on SDDe can improve the accuracy of the insulator discharge process and flashover voltage prediction, especially for the complex pollution area. During the generation and propagation of the arc, the leakage current under SDDm is relatively higher and the pollution layer resistance is lower compared to that under SDDe; the variations in the pollution layer resistance and leakage current with arc development under SDDm do not adequately reflect the actual conditions.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Zhang et al. (2026) studied this question.

synapsesocial.com/papers/69be36e36e48c4981c6762b6https://doi.org/10.3390/en19061531
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Impact of ESDD-standardised pollution on partial discharge inception and AC breakdown voltage of 11 kV disc insulators2026
  2. 2AC flashover voltage prediction of silicone rubber insulators under mechanical defects and non-uniform pollution using experimental, machine learning, and numerical approaches2026
  3. 3AC Icing Flashover Characteristics and Maximum Withstand Voltage Gradient of 220kV Polluted Composite Insulators2024 · 3 citations
  4. 4Flashover Model of Polluted Medium Voltage AC Indoor Insulators Around Electric Arc Nickle Furnace Roof2024 · 1 citations
  5. 5Examining electrical equivalent circuit models of insulators in transmission lines under pollution conditions: a comprehensive study and analysis2024 · 1 citations