Key points are not available for this paper at this time.
The synchronization instability in the presence of a fault is a main issue for the dynamic behavior and control of grid-feeding converters. In the literature, the synchronization stability assessment is carried out considering the dynamics of Phase-Locked Loops (PLL) but the transients of converter currents are neglected. The letter shows that such a simplification leads to inaccuracies and, thus, the current transients cannot be neglected. The letter proposes a model that captures the effect of such current transients on the converter synchronization. This model allows assessing the transient behavior and, hence, the stability, of power electronics converters with high accuracy, comparable, in fact, to EMT models. The fidelity of the proposed model is duly discussed in the case study.
Chen et al. (Mon,) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: