Accurate load forecasting can create both economic and reliability benefits for power system operators. However, the cyberattack on load forecasting may mislead operators to make unsuitable operational decisions for the electricity delivery. To effectively and accurately detect these cyberattacks, this paper develops a machine learning-based anomaly detection (MLAD) methodology. First, load forecasts provided by neural networks are used to reconstruct the benchmark and scaling data by using the k-means clustering. Second, the cyberattack template is estimated by the naive Bayes classification based on the cumulative distribution function and statistical features of the scaling data. Finally, the dynamic programming is utilized to calculate both the occurrence and parameter of one cyberattack on load forecasting data. A widely used symbolic aggregation approximation method is compared with the developed MLAD method. Numerical simulations on the publicly load data show that the MLAD method can effectively detect cyberattacks for load forecasting data with relatively high accuracy. Also, the robustness of MLAD is verified by thousands of attack scenarios based on Monte Carlo simulation.
No takes yet. Share an insight, caveat, or question.
Cui et al. (2019) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: