This is the authors' abstract. We don't add key points for this paper.
Having unveiled the problems associated with distance protection of lines connected to full-scale converter-interfaced renewable energy power plants (CIREPPs) due to remote and intermediate infeed in Part I of this paper, Part II describes why the countermeasures currently deployed by commercial relays to tackle these problems in a conventional power system fail in the presence of a CIREPP. Then, a new formula to calculate impedance is devised for the phase element of the relay to prevent maloperation in the event of line-to-line to ground faults. In addition, a communication-assisted method with minimal bandwidth requirement is proposed for balanced and line-to-line faults. The issues that should be taken into consideration for single-line-to-ground faults are also discussed. The solutions presented in this paper are simple and independent of the host system grid code, and can be applied to industrial memory-polarized distance relays. A comprehensive performance evaluation is presented to verify the reliable operation of the proposed methods.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Hooshyar et al. (2014) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: