Answers are grounded in this paper and cite their sources.
Wastewater treatment plants (WwTP) of combined sewer systems are designed to operate satisfactorily for the design case. Often this is a steady-state operation with high influent flow rates and pollutant loads at disadvantageous operating conditions (e.g. low water temperature and/or high sludge volume index). Consequently all plants maintain reserve capacities for most of the time, even during high storm water inflows. This paper reports of the development of an automatic control strategy to manage the wastewater flow to a WwTP according to its actual treatment capacity. The ammonia concentration in the nitrification zone and the sludge blanket level in the secondary clarifier were taken as key control parameters. The benefits of this novel control strategy were evaluated at a full scale plant (18 000pe) in Germany. The new system allowed the plant to process on average a stormwater flow 27% above the previous capacity. The plant could handle a maximum flow 45% above the design value while the effluent quality stayed within limits at all times. Our results show that combined storm water runoffs can significantly be reduced by enhancing the WwTP capacity by better flow management.
No takes yet. Share an insight, caveat, or question.
Müller et al. (1998) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: