Demonstrates detection of series arc faults in non-linear loads, indicating improved fire safety.
Series arc faults from partial disconnections are a major cause of electrical fires, yet extremely difficult to detect as their currents resemble normal loads. Under non-linear loads like Switched-Mode Power Supplies (SMPS), massive switching pulses mask high-frequency arc signals, causing critical Arc Fault Circuit Interrupter (AFCI) nuisance tripping. This paper proposes a Discrete Wavelet Transform (DWT)-based multi-resolution analysis to accurately detect series arcs under these complex conditions. To secure highly realistic simulation data, a 'Stochastic Modified Cassie Model' reflecting the physical intermittency of arc plasma was established. While conventional Fast Fourier Transform (FFT) failed due to SMPS harmonic masking and a lack of time-localization, the proposed DWT method successfully filtered the 15A-class SMPS pulses and 60Hz fundamental wave into the approximation coefficients. Consequently, it precisely isolated the asymmetrical, random high-frequency arc signals exclusively within the detail coefficient bands. This study mathematically proves that the DWT algorithm reliably diagnoses series arcs in non-linear environments, providing fundamental data for designing future intelligent fire prevention systems and mitigating AFCI nuisance tripping.
No takes yet. Share an insight, caveat, or question.
Kang et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: