Answers are grounded in this paper and cite their sources.
• Flow characteristics of thermal plumes above inclined heat sources were obtained. • Large eddy simulations were used to analyze velocity and temperature. • A formula of plume flow rate above inclined heat sources was verified. By utilizing the thermal plume effect of heat sources, high temperature building spaces can be effectively cooled to improve the internal thermal environment. This paper explores the flow characteristics of thermal plumes above heat sources with varying inclined angles. Visualization experiments were conducted to observe the flow trajectories of thermal plumes. Laboratory testing and large eddy simulations were utilized to analyze the distributions of velocity and temperature of the thermal plumes. The Rayleigh number is in a range of 10 8 –10 10 . The results show that as the angle increases from 15° to 75°, the plume axis shifts at Z/D = 6 ∼ 7 (15 ∼ 30°) and Z/D = 8 ∼ 9 (60 ∼ 75°). Additionally, a calculation formula for the flow rate of plumes above inclined area heat sources was obtained. The research findings offer insights into the design of natural ventilation systems in buildings with inclined area heat sources, thereby facilitating the creation of an optimal indoor environment.
No takes yet. Share an insight, caveat, or question.
Yang et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: