Answers are grounded in this paper and cite their sources.
A dead-time compensator for controlling higher-order processes with integral action and long dead-time is proposed. Tuning formulas are derived. If the velocity gain and the dead-time are estimated experimentally, only one parameter, the time constant defining the speed of the closed-loop setpoint response, has to be tuned manually. The same setpoint response is obtained as in the modified Smith predictor, while the load disturbance rejection is considerably faster.
No takes yet. Share an insight, caveat, or question.
Mataušek et al. (1999) studied this question.