This is the authors' abstract. We don't add key points for this paper.
Strict effluent quality standards and physical limitations of the equipment make accurately controlling dissolved oxygen (DO) concentration in wastewater treatment processes (WWTPs) a challenging task. In this paper, a data-driven model predictive control strategy with performance constraint (PC-MPC) is proposed to ensure accurate tracking of DO concentration set-point. First, a data-driven model is established using the fuzzy neural network, effectively addressing the problem of complex nonlinear modeling of WWTPs and providing accurate predictive output for the control process. Second, a model predictive control (MPC) strategy with performance constraint is designed, in which tracking error is considered as a performance constraint index within the MPC framework, enabling accurate tracking of the DO concentration to the desired set-point. Third, an adaptive constraint optimization algorithm based on the Levenberg-Marquardt (L-M) method is developed. By utilizing the exponential penalty function to reformulate the system constraints, the finite horizon optimization control problem can be directly solved to determine the optimal control sequence. Finally, the stability of the proposed PC-MPC strategy is proven through theoretical analysis and its effectiveness is validated on the benchmark simulation model No. 1.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2025) studied this question.
Synapse has enriched 8 closely related papers on similar clinical questions. Consider them for comparative context: