The paper establishes the linearised Phillips–Heffron model of a power system installed with a static synchronous compensator (STATCOM) and demonstrates the application of the model in analysing the damping effect of the STATCOM and designing a STATCOM stabiliser to improve power-system-oscillation stability. Both cases of single machine infinite bus and multimachine power systems are studied and example power systems are presented. These show the negative damping influence of a STATCOM DC voltage regulator on power system oscillations and the effectiveness of the STATCOM stabiliser superimposed on a STATCOM AC voltage regulator to counterattack the negative damping effect.