Key points are not available for this paper at this time.
A new approach to medium-voltage variable-frequency static AC motor drives offers improvements in power quality. Harmonic current injection into the power lines is below the most severe requirements of IEEE Standard 519-1992. The power factor of this new type of drive exceeds 94% at full load and is above 90% at 10% load. Motor voltage and current waveforms are improved so that torque pulsations are reduced. Peak voltage stress on motor insulation does not exceed peak input line voltage, and no zero sequence voltage is imposed. Drive efficiency exceeds 96%. This paper describes the new approach and some of the results achieved.
Building similarity graph...
Analyzing shared references across papers
Loading...
P.W. Hammond (Wed,) studied this question.
synapsesocial.com/papers/6a0d5639cae7912d2fa4eb6c — DOI: https://doi.org/10.1109/28.567113
P.W. Hammond
iRobot (United States)
IEEE Transactions on Industry Applications
Building similarity graph...
Analyzing shared references across papers
Loading...