Answers are grounded in this paper and cite their sources.
Inter-area oscillations in power networks are typically poorly controllable by means of local decentralized control. Recent research efforts have been aimed at developing wide-area control strategies that involve communication of remote signals. In conventional wide-area control strategies the control structure is fixed a priori typically based on modal criteria. In contrast, here we employ the recently introduced paradigm of sparsity-promoting optimal control to simultaneously identify the control structure and optimize the closed-loop performance. To induce a sparse control architecture, we regularize the standard quadratic performance index with an ℓ 1 -penalty on the feedback matrix. The quadratic objective functions are inspired by the classic slow coherency theory and are aimed at imitating homogeneous networks without inter-area oscillations. We use a compelling example to demonstrate that the proposed combination of the sparsity-promoting optimal control design with the slow coherency objective functions performs almost as well as the optimal centralized controllers.
No takes yet. Share an insight, caveat, or question.
Dörfler et al. (2013) studied this question.