Answers are grounded in this paper and cite their sources.
With the increasing installed capacity of wind power, the line-commutated converter-based high-voltage direct-current (LCC-HVDC) in sending AC grid encounters potential issues of sub/super-synchronous oscillations (SSSOs), posing a threat to the stable operation of power system. The impedance-based approach has proven to be a useful tool for investigating SSSOs in power electronic device-based systems, relying on the accurate impedance model. However, most existing studies on the stability of LCC-HVDC system simplify the receiving-side converter to an ideal DC voltage source, which ignores the AC-DC dynamics of the receiving-side converter and grid, causing inaccuracy in stability assessment. Moreover, there is a lack of clarity regarding the effect of the receiving-side system on oscillation stability. Thus, this paper establishes the complete impedance model of the LCC-HVDC considering the receiving-side system, by proposing a unified small signal transfer path framework for the LCC converter. Subsequently, the stability of the complete LCC-HVDC system is assessed, and the effect of the receiving-side system on the oscillation characteristics of SSSOs is investigated based on the DC impedance network in detail. Finally, a second-order quantitative index is defined to evaluate the influence factors on the receiving-side interaction, and the conditions for neglecting this interaction are discussed.
No takes yet. Share an insight, caveat, or question.
Li et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: