Large-signal impedance of grid-connected converters can be used to predict resonance-generated distortions in converter-grid systems. Note that the large-signal impedance of a network represents its impedance response for different magnitudes of perturbation injected at its terminals. This paper presents large-signal impedance-based modeling and mitigation of resonance of grid-connected voltage source converters. Challenges of large-signal modeling because of the inapplicability of the small-signal approximation are addressed by leveraging the dominating influence of hard nonlinearities (such as pulsewidth modulation saturation and limiters) over soft nonlinearities (such as Park's transformations and phase-locked loop (PLL)) in shaping the large-signal behavior of the converter. The paper develops large-signal gains of hard nonlinearities using different types of describing functions. The paper shows that the large-signal impedance of a voltage source converter (VSC) can be shaped to reduce resonance-generated distortions by inserting limiters in the control system of the VSC. Developed large-signal impedance models are validated using numerical simulations of a VSC with dq current control and PLL. Large-signal impedance measurements of a commercial 1 MW VSC-based inverter and a medium-voltage doubly-fed induction generator with approximate 4 MW rating are presented to experimentally demonstrate the influence of the injected perturbation magnitude on the impedance response.