Answers are grounded in this paper and cite their sources.
This paper proposes a harmonic calculation method, describes the methodologies to carry out steady-state harmonic performance studies at PCC point. Based on a small signal harmonic current and voltage sources injected to a large-scale AC system and MMC converters, the method can be used for harmonic characteristic calculation of the grid-connected MMC-HVDC and large AC system at Point of Common Coupling (PCC). To verify the proposed method, a typical offshore wind farm integrated into the AC system using a MMC-HVDC link model is built in the electromagnetic transient simulation software PSCAD/EMTDC. Simulation results of individual harmonic distortion (Dn) and Total Harmonic Distortion (THD) are calculated and compared with the analytical calculation values. The comparison results show correction and effectiveness of the proposed method.
No takes yet. Share an insight, caveat, or question.
Gu et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: