Answers are grounded in this paper and cite their sources.
Preheating / precooling the thermal mass of a building with off-peak electricity can significantly reduce demand for heating / cooling during peak periods. However, an unknown part of this load shifting process is dynamically determining the optimal preconditioning sequence. This paper puts forward a contextual bandits-based algorithm to dynamically optimize preconditioning behaviour. The analysis was conducted by employing a high-fidelity emulator in EnergyPlus, representing a generic small office building. The algorithm iteratively develops univariate change point models for different discrete preconditioning levels, enabling the estimation of a near-optimal preconditioning level for a given building and outdoor temperature forecast for the day. HVAC-related electricity cost savings achieved through this adaptive algorithm varied between 10 and 40% for different peak pricing and envelope scenarios. For all peak pricing and envelope scenarios, the adaptive algorithm was superior to the baseline preconditioning sequences and within 2% of those estimated using a global optimization approach.
No takes yet. Share an insight, caveat, or question.
Gunay et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: