The Proportional-Integral-Derivative (PID) is by far the most commoncontroller in process industries. In practice, a problem with PID controllers mayarise when the controlled process variable (PV) saturates. At this point, the error,i.e., the difference between the set point (SP) and PV becomes constant, and so thederivative control action becomes zero or backs off. This leads to a sudden increasein the total controller output and as a result the process variable moves above itslimit showing larger overshoot and settling time. To solve this problem, it isproposed to modify the PID controller action when the PV saturates. Themodification is simply to multiply the derivative part by a suitable gain, transfer itto the integral part, and then the derivative part is set to zero. When the processoutput later becomes unsaturated, the derivative action is activated again. Thistechnique is shown to reduce the overshoot, settling time, integral of absolute error(IAE), and works well in the presence of measurement noise. Although the optimalvalue of the gain depends on the size of disturbance which is not usually known, afixed value of 2 is shown to be reasonable for most levels of disturbance.