This is the authors' abstract. We don't add key points for this paper.
This study presents a method for high-impedance fault (HIF) detection in a low-voltage DC (LVDC) distribution system via mathematical morphology (MM), which is composed of two elementary transformations, namely, dilation and erosion. Various MM-based filters are used to detect abnormal signals of current waveform. The LVDC distribution system, including power conversion devices, such as AC/DC and DC/DC converters, is modelled with electromagnetic transient program (EMTP) software to verify the proposed method. The HIF arc model in the DC system is also implemented with EMTP/MODELS, which is a symbolic language interpreter for EMTP. Simulation results show that the proposed method can be applied to detect HIF effectively in the LVDC distribution system.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Oh et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: