Answers are grounded in this paper and cite their sources.
This article analyzes the various types of saturation effects implemented in second-order synchronous generator dynamic models commonly used in power system stability studies. The concept and principles of the saturation effects for each model are discussed, focusing on the accuracy of the modeled field current and how the implemented saturation effect affects the synchronous generator parameter validation. The article also reveals a drawback of the saturation function implemented in the GENTPJ model and clarifies a misconception of the GENTPJ saturation function through theoretical analysis and comparison of saturation characteristic curves provided by generator manufacturers. Furthermore, the article demonstrates the advantage of separating synchronous generator magnetic saturation from its field current accuracy using the WECC-approved GENQEC model for power system stability study.