Answers are grounded in this paper and cite their sources.
Presents a procedure for obtaining time-domain solutions for faulted power systems containing multiple rotating machines. The time-domain solutions are obtained using a combination of both time and steady-state frequency-domain techniques. The transmission network is modeled using steady-state AC techniques, while the rotating machines are represented by sets of coupled differential equations. The interface between the time-domain machine models and the frequency-domain transmission network model transforms the differential equation solutions into the appropriate frequency-domain phasors. The combination of time and frequency-domain analysis allows the total number of calculations required for a solution to be considerably less than the number required for a complete time-domain solution.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
No takes yet. Share an insight, caveat, or question.
Halpin et al. (2002) studied this question.
Synapse has enriched one closely related paper. Consider it for comparative context: