Answers are grounded in this paper and cite their sources.
A strategy for volt/VAr control in distribution systems is described. The aim is to determine optimum dispatch schedules for on-load tap changer (OLTC) settings at substations and all shunt capacitor switching based on the day-ahead load forecast. To reduce switching operations for OLTC at substations, a time-interval based control strategy is adopted that decomposes a daily load forecast into several sequential load levels. A genetic algorithm based procedure is used to determine both the load level partitioning and the dispatch scheduling. The proposed strategy minimises the power loss and improves the voltage profile for a whole day across the whole system, whilst ensuring that the number of switching operations is less than the maximum daily allowance. A comparison of numerical studies and their associated results illustrates both the feasibility and the effectiveness of the proposed strategy.
No takes yet. Share an insight, caveat, or question.
Hu et al. (2003) studied this question.