Grid-connected inverters typically use phase-locked loops (PLL) to obtain the grid voltage phase and implement DC voltage control to maintain DC voltage's stability. However, since the time scale of both PLL and DC voltage control loop is approximately 100 milliseconds, there are interactions between the two during the dynamics. As the grid strength weakens, their dynamic coupling increases. This poses a significant threat to system's safe and stable operation in weak grid. In this paper, a decoupling control scheme based on the real-time adjustment of the dq-axis current references is proposed to improve the system's stability in weak grid conditions. Firstly, the small-signal model of grid-connected voltage source converter (VSC) is developed to study system's small-signal stability. Then, eigenvalue analysis shows that the coupling effect of PLL and DC voltage control reduces the system's stability. For this purpose, a decoupling control scheme is proposed. By comparing the eigenvalue distribution and participation factors before and after decoupling, the proposed scheme is proved to improve the system's small-signal stability. Finally, simulations based on PowerFactory are carried out to verify correctness of the theoretical analysis and effectiveness of the proposed decoupling control scheme.