Answers are grounded in this paper and cite their sources.
This paper outlines a reduced-order aggregate dynamical model for parallel-connected single-phase grid-connected inverters. For each inverter, we place no restrictions on the converter topology and merely assume that the ac-side switch-averaged voltage can be controlled via pulsewidth modulation. The ac output of each inverter interfaces through an LCL filter to the grid. The closed-loop system contains a phase locked loop for grid synchronization, and real- and reactive-power control are realized with inner and outer PI current- and power-control loops. We derive a necessary and sufficient set of parametric relationships to ensure that a reduced-order aggregated state-space model for an arbitrary number of such paralleled inverters has the same model order and structure as any single inverter. We also present reduced-order models for the settings where the real- and reactive-power setpoints are different and where the inverters have different power ratings. We anticipate the proposed model being useful in analyzing the dynamics of large collections of parallel-connected inverters with minimal computational complexity. The aggregate model is validated against measurements obtained from a multi-inverter experimental setup consisting of three 750-VA paralleled grid-connected inverters, hence establishing robustness of the analytical result to parametric variations seen in practice.
No takes yet. Share an insight, caveat, or question.
Purba et al. (2018) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: