The presence of low-frequency and low-dampened oscillation modes can compromise the operating stability of power systems. Recent research has shown that the use of phasor measurement units data to compose a wide-area damping controller (WADC) has been shown to be effective in mitigating such oscillation modes but the possibility of loss of communication channels due to cyber-attacks or failures can compromise the proper operation of this controller. Besides, traditional control design methods present difficulties for the WADC control design. This article proposes a method based on hybrid particle swarm optimization in order to design a WADC that ensures robustness to power system-operating uncertainties, time delays variations on the WADC channels, and the permanent failure of the WADC communication channels. Modal analysis and nonlinear time-domain simulations were conducted in the IEEE 68-bus power system considering a set of scenarios.