By increasingly relying on network-based operation for control, monitoring, and protection functionalities, modern wide-area power systems have also become vulnerable to cyber-attacks aiming to damage system performance and/or stability. Resilience in state-of-the-art methods mostly relies on known characteristics of the attacks and static control loops (i.e., with fixed input/output channels). This work proposes a `dynamic loop' wide-area damping strategy, where input/output channel pairs are changed dynamically. We study `reactive' dynamic switching in case of detectable attack and `pro-active' dynamical switching, in case of undetectable (stealth) attacks. Stability of the dynamic loop is presented via Lyapunov theory, under parametric perturbations, average dwell time switching and external perturbations. Using two- and five-area IEEE benchmarks, it is shown that the proposed strategy provides effective damping and robustness under various detectable (e.g., false data injection, denial-of-service) and stealth (replay, bias injection) attacks.
No takes yet. Share an insight, caveat, or question.
Patel et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: