Answers are grounded in this paper and cite their sources.
This paper presents dc-bus voltage control with a three-phase bidirectional inverter for dc distribution systems. The bidirectional inverter can fulfill both grid connection and rectification modes with power factor correction. The proposed control includes two approaches, one line-cycle regulation approach (OLCRA) and one-sixth line-cycle regulation approach (OSLCRA), which take into account dc-bus capacitance and control dc-bus voltage to track a linear relationship between the dc-bus voltage and inverter inductor current. Since both of the approaches require the parameter of dc-bus capacitance, this paper first presents determination of dc-bus capacitor size and an online capacitance estimation method. With the OLCRA, the inverter tunes the dc-bus voltage every line cycle, which can reduce the frequency of operation-mode change and current distortion. The OSLCRA adjusts current command every one-sixth line cycle to adapt to abrupt dc-bus voltage variation. The two approaches together can prevent dc-bus voltage from wide variation and improve the availability of the dc distribution systems without increasing dc-bus capacitance. Experimental results measured from a three-phase bidirectional inverter have verified the feasibility of the discussed control approaches.
No takes yet. Share an insight, caveat, or question.
Wu et al. (2012) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: