Answers are grounded in this paper and cite their sources.
Investigates grid-forming energy storage strategies for voltage and frequency support in power systems, indicating implications for renewable integration.
This paper addresses the “dual-high” challenges posed by high proportions of renewable energy and power electronic equipment in new power systems, and investigates the active support characteristics of grid-forming energy storage stations in terms of voltage and frequency. Regarding voltage support, the paper analyzes the transient process of a three-phase short-circuit fault in the power grid and proposes a low-voltage ride-through control strategy based on the flexible adjustment of active power and voltage commands. By suppressing short-circuit currents and power-angle instability during the fault, this strategy effectively enhances the system’s transient stability. The effectiveness of this strategy when the grid voltage drops to zero was verified through PSCAD/EMTDC simulations. Regarding frequency support, a small-signal model for frequency regulation of grid-forming converters was established, revealing the influence of controller parameters on the system’s virtual inertia. Simulation results indicate that grid-forming control possesses adjustable inertial support capabilities, effectively enhancing the system’s frequency stability. This research provides a theoretical basis and control strategy support for the application of grid-forming energy storage stations in power grids with a high proportion of renewable energy.
No takes yet. Share an insight, caveat, or question.
Guo et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: