We have analyzed and modeled the constraints on the protection system of a low-voltage facility-power system due to integration of an inverter-coupled renewable energy (RE) source. A common system topology is considered where some of the facility loads can be fed from the PV battery energy storage system (PV-BESS) utilizing an automatic transfer switch. For understanding the effect of the size of such RE sources and the range of resulting short-circuit currents which may cause a loss of sensitivity for the protection devices, we have analyzed short-circuit currents from utility, generator and then the PV-BESS. The results of the derived model shows that there is a lower limit on the size of the RE source which in our case is a PV-BESS. The model and the analysis are verified by commercially available short-circuit analysis software ETAP®. The analysis also shows the limits and the constraints on the protection devices for maintaining their sensitivity to fault currents when such an RE source is to be allowed to power facility-loads.