In this paper, Three Phase Shunt Active Harmonic Filter is used for harmonic compensation of fully Controlled loads by using new thyristorized Pulse Generator Circuits which generates 12 Pulses for two Non-Linear three phase Loads. The three phase Non-Linear Loads are connected at the secondary of three phase Transformers with Three Phase Breakers having Transition time 5/60seconds. A new Pulse Generator topology is used for generating pulses for each of three phase non-linear loads. The Circuit used for Compensation of Harmonics having three phase IGBT based Inverter. The IGBT base d Shunt Active Harmonic Filter gets firing Pulses from PLL phase Locked Loop& Hysteresis Switching HS. The used PLL extracts the Fundamental component of load current which is then multiplied with same RMS gain for generating the Reference current for Hysteresis Current Controller. The used Hysteresis Current Controller compares the reference current with measured current of Shunt Active Harmonic Filter for generating the pulse for three phase IGBT Inverter.