This article proposes direct power control (DPC) associated with space vector modulation (SVM) for a shunt active power filter (SAPF). This control is suggested in order to overcome the drawbacks of the conventional DPC, where the SVM is able to decrease the high active and reactive power ripples maintaining a fixed switching frequency. In addition, the performance of the proposed scheme is improved by replacing PI controllers with supertwisting second-order sliding mode controllers (ST-SMCs) in the active and reactive power control loops. This technique provides high robustness and dynamics for external perturbations. The proposed control DPC-SVM based on ST-SMC is investigated by simulation and practical implementation using MATLAB/Simulink with a real-time interface based on a dSPACE 1104 board.
No takes yet. Share an insight, caveat, or question.
Ouchen et al. (2020) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: